Wednesday, October 28, 2020

Temperature Sensors Used for Power Generation

Temperature Sensors for Power Plants

In an electrical generating plant, most temperature measurements are performed with RTDs (resistance temperature detectors) and thermocouples (T/Cs). 

RTD's are sensors that produce a measurable change in electrical resistance, while thermocouples have a change in mV signal in response to temperature change. 

RTD's consist of a thin conductor (nickel, platinum, copper) wrapped around a glass or ceramic bobbin, placed into a protective sheath, and backfilled with an electrically inert material but thermally conductive. 

Power plants use 100-ohm platinum, 100-ohm nickel, 120-ohm nickel, and 10-ohm copper RTDs. Though offering excellent accuracy and long-term reliability, RTDs are vulnerable to mechanical shock and vibration in a generating plant. They are more costly than thermocouples and are generally limited to about 1110 ° F. A very appealing feature for RTDs is their electrical noise immunity, a significant advantage over thermocouples. Finally, inexpensive instrument wire is all that is required to connect the RTD to the measuring instrumentation. 

A thermocouple consists of two wires made of dissimilar alloys, joined at both ends. One junction is coined the "hot junction," the other is the "cold junction" (or reference junction). When the hot junction experiences temperature change, a voltage is produced proportional to the temperature difference between hot and cold junctions. 

T/Cs are made of various alloy combinations and "calibrations" for different temperature ranges. Type J, K and N are the most common thermocouples for power generation applications below 1800 ° F; R and S types are common for applications above 1800 ° F. Besides the evident higher temperature capacity, thermocouples have a quicker response and greater endurance to shock and vibration. However, thermocouples are more susceptible to conducted and radiated electrical noise due to the minute signals generated. Another problem with thermocouples is their deterioration over time when used at high temperatures, hence being less stable than RTDs. One final concern is running an expensive thermocouple extension wire of the same type as the sensor-measuring instrument thermocouple.

Duro-Sense Corporation
310-533-6877
https://duro-sense.com

Friday, May 25, 2018

Power Plant Temperature Sensors

Power plants (generating facilities) transform the mechanical energy of a spinning generator into electrical energy. Heat (from flame, nuclear reaction, or chemical reaction) is used to create steam that, in turn, produces the mechanical energy to drive turbines. There are many areas where precision temperature measurement and monitoring is critical to keep power plant systems running. Thermocouples and RTD sensors provide accurate, repeatable, and reliable  measurement.

Duro-Sense
https://duro-sense.com
Phone: 310-533-6877


Saturday, April 14, 2018

Thermocouples and RTDs Used in Power Plants

Thermocouple and RTD Used in Power Plants
The majority of temperature measuring in a electrical generating plant are done with RTDs (resistance temperature detectors) and thermocouples (T/Cs).

RTD's are devices that produce a measurable resistance change with temperature change, while thermocouples produce a mV signal change in response to temperature change.

RTD's are constructed of a a thin conductor (nickel, platinum, copper) wrapped around a glass or ceramic bobbin, inserted into a protective sheath, and backfilled with an electrically inert, but thermally conductive, material.

Power plants historically use 100-ohm platinum, 100-ohm nickel, 120-ohm nickel, and 10-ohm copper RTDs. While providing excellent accuracy and long term stability, RTDs are prone to mechanical shock and vibration found in a generating facility. They are more expensive than thermocouples and application temperatures are generally limited to around up to 1110°F. One very attractive feature for RTDs are their inherent electrical noise immunity, a significant advantage over thermocouples. Finally, common, inexpensive instrument wire is used for connecting the RTD to the measuring instrumentation.

A thermocouple consists of two wires, made of dissimilar alloys, joined together at each end. One junction is designated the hot junction, the other junction is designated as the cold (or reference junction). When the hot junction experiences a change in temperature, a voltage is generated that is proportional to the difference in temperature between the hot and cold junctions. 

T/Cs are be made of different combinations of alloys and "calibrations" for use at various temperature ranges. The most common thermocouples for the power generation industry applications under 1800 °F are type are J, K and N ; for applications over 1800 °F,  types R and S are common. Aside from the obvious higher temperature capability, thermocouples provide faster response and greater shock and vibration endurance. However, thermocouples, due to the minuter signals the produce, are more susceptible to conducted and radiated electrical noise.  Another concern with thermocouples are their degradation over time when used at elevated temperatures and are therefore less stable than RTDs. One final issue is the need to run costly thermocouple extension wire of the same type as the thermocouple between sensor and measuring instrument.

When in doubt about which sensor is best to apply in a power plant application, contact an application expert who will help you choose the ideal sensor for your requirements.